New South Wales variation · NCC 2022 Volume One

NSW J1P1 Energy use

NSW Part J1 Energy efficiency performance requirements · varies J1P1 Energy use

Open on NCC Online ↗

A building including its services, must have features that facilitate the efficient use of energy appropriate to—

the function and use of the building; and

the level of human comfort required for the building use; and

solar radiation being—

utilised for heating; and

controlled to minimise energy for cooling; and

the energy source of the services; and

the sealing of the building envelope against air leakage; and

for a conditioned space, achieving an hourly regulated energy consumption, averaged over the annual hours of operation, of not more than—

for a Class 6 building, 80 kJ/m².hr; and

for a Class 5, 7b, 8 or 9a building other than a ward area, or a Class 9b school, 43 kJ/m².hr; and

for all other building classifications, 15 kJ/m².hr.

Applications

NSW J1P1 does not apply to a Class 2 building or a Class 4 part of a building.

Changed in NCC 2025. See NCC 2025 Volume One NSW J1P1, or show what changed.

Insert NSW clause J1P1 in clause J1P1 as follows: A building including its services, must have features that — facilitate the efficient use of energy and near zero operational greenhouse gas emissions appropriate to — the function and use of the building; and the level of human comfort required for the building use; and solar radiation being — utilised for heating; and controlled to minimise energy for cooling; and the energy source of the services; and the sealing of the building envelope against air leakage; and for a conditioned space, achieving achieve an hourly regulated energy consumption, consumption and associated greenhouse gas emissions, averaged over the annual hours of operation, of not more than — for a Class 6 building, 80 40 kJ/m².hr; and 4 g of CO2-e/m2.hr; and for a Class 5, 7b, 8 or 9a building other than a ward area, or a Class 9b school, 43 kJ/m².hr; 22 kJ/m².hr, and 2.2 g of CO2-e/m2.hr; and for all other building classifications, 15 kJ/m².hr. Applications NSW J1P1 does not apply to a Class 2 building or a Class 4 part 8 kJ/m².hr and 1 g of a building. CO2-e/m2.hr.

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause