New South Wales variation · NCC 2022 Volume One

NSW J7D4 Interior artificial lighting and power control

Part J7 Artificial lighting and power · varies J7D4 Interior artificial lighting and power control

Open on NCC Online ↗

Delete subclause J7D4(4) and insert NSW J7D4(4) as follows:

(4) 95% of the light fittings in a building or storey of a building, other than a Class 3 building of more than 250 m2 must be controlled by—

a time switch in accordance with Specification 40; or

an occupant sensing device such as—

a security key card reader that registers a person entering and leaving the building; or

a motion detector in accordance with Specification 40.

Changed in NCC 2025. See NCC 2025 Volume One NSW J7D4, or show what changed.

Delete subclause J7D4(4) J7D4(1) and insert NSW J7D4(4) J7D4(1) as follows: (4) 95% of the light fittings (1) This subclause does not apply in a building or storey of a building, other than NSW. Delete subclause J7D4(2) and insert NSW J7D4(2) as follows: (2) Subject to (3) to (12), in a Class 3 building of more than 250 m2 and Class 5 to 9 building all artificial lighting must be controlled by — a time switch in accordance with Specification 40; or an occupant sensing device such as — a security key card reader that registers a person entering and leaving the building; or a motion detector demand-operated control devices in accordance with Specification 40.

Removed words are struck through; added words are highlighted. Comparison of the text only.