Northern Territory variation · NCC 2022 Volume One

NT F7D5 Sound insulation of walls between units

NT Part F7 Sound transmission and insulation · varies F7D5 Sound insulation rating of floors

Open on NCC Online ↗

A wall must have an RW not less than 45 if it separates—

sole-occupancy units; or

a sole-occupancy unit not within a Class 9c building from a plant room, lift shaft, stairway, public corridor, hallway or the like; or

a sole-occupancy unit in a Class 9c building from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room.

Changed in NCC 2025. See NCC 2025 Volume One NT F7D5, or show what changed.

Insert NT clause F7D5 in clause F7D5 as follows: A wall must have an RW not less than 45 … being an associated ensuite), laundry, plant room or utilities room.

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause