Northern Territory variation · NCC 2022 Volume One

NT S28C2 Construction deemed-to-satisfy

Specification 28 Sound insulation for building elements · varies S28C2 Discontinuous construction

Open on NCC Online ↗

Delete clause S28C2 and insert NT S28C2 as follows:

The forms of construction listed in NT S28C3 are considered to have the RW stated in that clause if installed as follows:

Masonry: units must be laid with all joints filled solid, including those between the masonry and any adjoining construction.

Concrete slabs: joints between concrete slabs and any adjoining construction must be filled solid.

Plasterboard—

if one layer is required under this Specification, it must be screw-fixed to the studs with joints staggered on opposite faces; and

if 2 layers are required, the first layer must be fixed according to (i) and the second layer must be fixed to the first layer with nails, screws or adhesive so that the joints do not coincide with those of the first layer; and

joints between sheets or between sheets and any adjoining construction must be taped and filled solid; and

fire-protective grade plasterboard must be the special grade manufactured for use in fire-resisting construction.

Steel studs and perimeter members—

the section of steel must be not less than 0.6 mm thick; and

studs must be not less than 63 mm in depth unless another depth is listed in NT S28C3; and

studs must be fixed to steel top and bottom plates of sufficient depth to permit secure fixing of the plasterboard; and

all steel members at the perimeter of the wall must be securely fixed to the adjoining structure and be bedded in resilient compound or the joints must be caulked so that there are no voids between the steel members and the wall.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One NT S28C2.