NCC 2022 Volume One
Part C1 Fire resistance
18 clauses · Open on NCC Online ↗
- C1O1 ObjectiveThe Objective of Parts C1, C2, C3 and C4 is to— safeguard people from illness or injury due to a fire in a building; and safeguard occupants from…
- C1F1 Structural stability during a fireA building is to be constructed to maintain structural stability during fire to— allow occupants time to evacuate safely; and allow for fire brigade…
- C1F2 Prevention of fire spreadA building is to be provided with safeguards to prevent fire spread— so that occupants have time to evacuate safely without being overcome by the…
- C1P1 Structural stability during a fireA building must have elements which will, to the degree necessary, maintain structural stability during a fire appropriate to— the function or use…
- C1P2 Spread of fireA building must have elements which will, to the degree necessary, avoid the spread of fire— to exits; and to sole-occupancy units and public…
- C1P3 Spread of fire and smoke in health and residential care buildingsA building must be protected from the spread of fire and smoke to allow sufficient time for the orderly evacuation of the building in an emergency.…
- C1P4 Safe conditions for evacuationTo maintain tenable conditions during occupant evacuation, a material and an assembly must, to the degree necessary, resist the spread of fire and…
- C1P5 Behaviour of concrete external walls in a fireA concrete external wall that could collapse as a complete panel (e.g. tilt-up and pre-cast concrete) must be designed so that in the event of fire…
- C1P6 Fire protection of service equipmentA building must have elements, which will, to the degree necessary, avoid the spread of fire from service equipment having— a high fire hazard; or a…
- C1P7 Fire protection of emergency equipmentA building must have elements, which will, to the degree necessary, avoid the spread of fire so that emergency equipment provided in a building will…
- C1P8 Fire protection of openings and penetrationsAny building element provided to resist the spread of fire must be protected, to the degree necessary, so that an adequate level of performance is…
- C1P9 Fire brigade accessAccess must be provided to and around a building, to the degree necessary, for fire brigade vehicles and personnel to facilitate fire brigade…
- Table C1V1 Fire spread between buildings on adjoining allotmentsColumn 1 (Location) | Column 2 (Heat flux (kW/m2)) On boundary | 80 1 m from boundary | 40 3 m from boundary | 20 6 m from boundary | 10
- C1V1 Fire spread between buildings on adjoining allotmentsCompliance with C1P2(1)(c) to avoid the spread of fire between buildings on adjoining allotments is verified when it is calculated that— a building…
- Table C1V2 Fire spread between buildings on the same allotmentColumn 1 (Distance between buildings on the same allotment (m)) | Column 2 (Heat flux (kW/m2)) 0 | 80 2 | 40 6 | 20 12 | 10
- C1V2 Fire spread between buildings on the same allotmentCompliance with C1P2(1)(c) to avoid the spread of fire between buildings on the same allotment is verified when, for the distances between buildings…
- C1V3 Fire spread via external wallsCompliance with C1P2 to avoid the spread of fire via the external wall of a building is verified when— compliance with C1P2(1)(c) to avoid the…
- C1V4 Fire Safety Verification MethodCompliance with C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8 and C1P9 is verified when a building is designed in accordance with— the requirements…