Verification Method · NCC 2022 Volume One

C1V1 Fire spread between buildings on adjoining allotments

Part C1 Fire resistance · NCC 2019: CV1

Open C1V1 on NCC Online ↗

Compliance with C1P2(1)(c) to avoid the spread of fire between buildings on adjoining allotments is verified when it is calculated that—

a building will not cause heat flux in excess of those set out in Column 2 of Table C1V1 at the location on an adjoining property set out in Column 1 of Table C1V1; and

when located at the distances from the allotment boundary set out in Column 1 of Table C1V1, a building is capable of withstanding the heat flux set out in Column 2 of Table C1V1 without ignition.

Table C1V1 Fire spread between buildings on adjoining allotments

Column 1 (Location)

Column 2 (Heat flux (kW/m2))

On boundary

80

1 m from boundary

40

3 m from boundary

20

6 m from boundary

10