Part J9 Energy monitoring and on-site distributed energy resources
6 clauses · Open on NCC Online ↗
- J9D1 Deemed-to-Satisfy Provisions NSWWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements J1P1 to J1P4 are satisfied by complying with— J2D2; and J3D2 to J3D15; and…
- J9D2 Application of PartThe Deemed-to-Satisfy Provisions of this Part do not apply— within a sole-occupancy unit of a Class 2 building or a Class 4 part of a building; or…
- J9D3 Facilities for energy monitoringA building or sole-occupancy unit with a floor area of more than 500 m2 must have energy meters configured to record the time-of-use consumption of…
- Table J9D4 Electric vehicle distribution board requirement for each storey of a carparkCarpark spaces per storey for electric vehicles | Electrical distribution boards for electric vehicle charging per storey 0 - 9 | 0 10 - 24 | 1 25 -…
- J9D4 Facilities for electric vehicle charging equipmentSubject to (2), a carpark associated with a Class 2, 3, 5, 6, 7b, 8 or 9 building must be provided with electrical distribution boards dedicated to…
- J9D5 Facilities for solar photovoltaic and battery systemsThe main electrical switchboard of a building must— contain at least two empty three-phase circuit breaker slots and four DIN rail spaces labelled…