S10C2 General requirements
Specification 10 Fire-protected timber · NCC 2019: Spec C1.13a: 2.1
(1) Fire-protected timber must—
utilise a non-combustible fire-protective covering fixed in accordance with the system requirements to achieve an FRL not less than that required for the building element; and
have a non-combustible fire-protective covering fixed in accordance with system requirements—
to achieve a resistance to the incipient spread of fire of not less than 45 minutes when tested in accordance with—
for horizontal elements — Section 4 of AS 1530.4; and
for other elements — the relevant test procedures from Section 4 of AS 1530.4 applied to the element lining; or
which consists of not less than 2 layers of 13 mm thick, fire-protective grade plasterboard.
(2) For the purposes of (1), the non-combustible fire-protective covering provided under (1)(b) may form all or part of the non-combustible fire-protective covering provided under (1)(a).