S10C2 General requirements

Specification 10 Fire-protected timber · NCC 2019: Spec C1.13a: 2.1

Open S10C2 on NCC Online ↗

(1) Fire-protected timber must—

utilise a non-combustible fire-protective covering fixed in accordance with the system requirements to achieve an FRL not less than that required for the building element; and

have a non-combustible fire-protective covering fixed in accordance with system requirements—

to achieve a resistance to the incipient spread of fire of not less than 45 minutes when tested in accordance with—

for horizontal elements — Section 4 of AS 1530.4; and

for other elements — the relevant test procedures from Section 4 of AS 1530.4 applied to the element lining; or

which consists of not less than 2 layers of 13 mm thick, fire-protective grade plasterboard.

(2) For the purposes of (1), the non-combustible fire-protective covering provided under (1)(b) may form all or part of the non-combustible fire-protective covering provided under (1)(a).

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S10C2.