Specification 10 Fire-protected timber · NCC 2019: Spec C1.13a: 3.2

Open S10C5 on NCC Online ↗

An Accredited Testing Laboratory may carry out the test specified in S10C4 at pilot scale provided—

a specimen (which must be not less than 1000 mm x 1000 mm) adequately represents the proposed construction in the building; and

the fire resistance of the specimen has already been determined in a full scale test performed in accordance with AS 1530.4 to demonstrate adequate retention of the fire protection system in conjunction with the timber elements being protected; and

the results of the test do not apply to construction larger than limits defined by the Accredited Testing Laboratory conducting the pilot examination.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S10C5.