Specification clause · NCC 2025 Volume One
S10C5 Smaller specimen permitted
Specification 10 Fire-protected timber · NCC 2019: Spec C1.13a: 3.2
An Accredited Testing Laboratory may carry out the test specified in S10C4 at pilot scale provided—
a specimen (which must be not less than 1000 mm x 1000 mm) adequately represents the proposed construction in the building; and
the fire resistance of the specimen has already been determined in a full scale test performed in accordance with AS 1530.4 to demonstrate adequate retention of the fire protection system in conjunction with the timber elements being protected; and
the results of the test do not apply to construction larger than limits defined by the Accredited Testing Laboratory conducting the pilot examination.