Specification clause · NCC 2022 Volume One

S12C4 Construction Deemed-to-Satisfy for smoke doors

Specification 12 Fire doors, smoke doors, fire windows and shutters · NCC 2019: Spec C3.4: 3.2

Open S12C4 on NCC Online ↗

A smoke door of one or two leaves satisfies S12C3 if it is constructed as follows:

The leaves are side-hung to swing—

in the direction of egress; or

in both directions.

The leaves are solid-core and at least 35 mm thick, or are capable of resisting smoke at 200°C for 30 minutes.

The leaves are fitted with smoke seals.

The leaves—

are normally in the closed position; or

operate such that—

they are closed automatically with the automatic closing operation initiated by smoke detectors, installed in accordance with the relevant provisions of AS 1670.1, located on each side of the doorway not more than 1.5 m horizontal distance from the doorway; and

in the event of power failure to the door, they will fail-safe in the closed position.

The leaves return to the fully closed position after each manual opening.

Any glazing incorporated in the door complies with AS 1288.

If a glazed panel is capable of being mistaken for an unobstructed exit, the presence of the glass must be identified by an opaque mid-height band, mid-rail, crash-bar or other opaque construction.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S12C4.