Specification 12 Fire doors, smoke doors, fire windows and shutters · NCC 2019: Spec C3.4: 4
A required fire shutter must—
be a shutter that—
is identical with a tested prototype that has achieved the required FRL; and
is installed in the same manner and in an opening that is not larger than the tested prototype; and
did not have a rise in average temperature on the side remote from the furnace of more than 140 K during the first 30 minutes of the test; or
be a steel shutter complying with AS 1905.2 if a metallic fire shutter is not prohibited by C4D6.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S12C5.