Specification clause · NCC 2022 Volume One
S12C6 Fire windows
Specification 12 Fire doors, smoke doors, fire windows and shutters · NCC 2019: Spec C3.4: 5
A required fire window must be—
identical in construction with a prototype that has achieved the required FRL; and
installed in the same manner and in an opening that is not larger than the tested prototype.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S12C6.