Specification clause · NCC 2022 Volume One

S16C2 Fixed or moveable ramp

Specification 16 Accessible water entry/exit from swimming pools · NCC 2019: Spec D3.10: 2

Open S16C2 on NCC Online ↗

A fixed or moveable ramp must—

have a slip-resistant surface; and

have a maximum gradient of 1:14; and

have handrails complying with the requirements for ramps in AS 1428.1, installed on both sides of the ramp; and

have kerbs in accordance with the requirements for ramps in AS 1428.1; and

extend to a depth of not less than 900 mm and not more than 1100 mm below the stationary water level; and

have landings in accordance with the requirements for ramps in AS 1428.1, with a landing located at the bottom and top of each ramp and a landing must be located at a level between 900 mm and 1100 mm below the stationary water level.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S16C2.