Specification clause · NCC 2025 Volume One
S16C2 Fixed or moveable ramp
Specification 16 Accessible water entry/exit from swimming pools · NCC 2019: Spec D3.10: 2
A fixed or moveable ramp must—
have a slip-resistant surface; and
have a maximum gradient of 1:14; and
have handrails complying with the requirements for ramps in AS 1428.1, installed on both sides of the ramp; and
have kerbs in accordance with the requirements for ramps in AS 1428.1; and
extend to a depth of not less than 900 mm and not more than 1100 mm below the stationary water level; and
have landings in accordance with the requirements for ramps in AS 1428.1, with a landing located at the bottom and top of each ramp and a landing must be located at a level between 900 mm and 1100 mm below the stationary water level.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S16C2.