Specification clause · NCC 2022 Volume One

S17C12 Residential care buildings

Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 12

Open S17C12 on NCC Online ↗

(1) In addition to the provisions of AS 2118.4, a sprinkler system in—

a Class 3 building used as a residential care building; or

a Class 9a health-care building used as a residential care building; or

a Class 9c building,

must comply with sub-clause (2).

(2) Any sprinkler system referred to in (1) must—

be provided with a monitored main stop valve in accordance with AS 2118.1; and

be permanently connected with a direct data link or other approved monitoring system to a fire station or fire station dispatch centre.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S17C12.