Specification clause · NCC 2022 Volume One
S17C12 Residential care buildings
Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 12
(1) In addition to the provisions of AS 2118.4, a sprinkler system in—
a Class 3 building used as a residential care building; or
a Class 9a health-care building used as a residential care building; or
a Class 9c building,
must comply with sub-clause (2).
(2) Any sprinkler system referred to in (1) must—
be provided with a monitored main stop valve in accordance with AS 2118.1; and
be permanently connected with a direct data link or other approved monitoring system to a fire station or fire station dispatch centre.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S17C12.