Specification clause · NCC 2022 Volume One
S17C13 Sprinkler systems in lift installations
Specification 17 Fire sprinkler systems · NCC 2019: Spec E1.5: 13
(1) Where sprinklers are installed in a space housing lift electrical and control equipment, including machine rooms, secondary floors and sheave rooms, sprinklers in these spaces must—
have heads protected from accidental damage by way of a guard that will not impair the performance of the head; and
be capable of being isolated and drained, either separately or collectively, without isolating any other sprinklers within the building.
(2) Valves provided to control sprinklers referred to in (1) must be installed in accordance with S17C10(2).
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S17C13.