S21C4 Smoke reservoirs

Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 4

Open S21C4 on NCC Online ↗

(1) A fire compartment must be divided at ceiling level into smoke reservoirs formed by smoke baffles/curtains of non-combustible and non-shatterable construction.

(2) The horizontal area of a smoke reservoir must not exceed 2000 m2 and in enclosed walkways and malls of a Class 6 building must not exceed 60 m in length.

(3) Smoke reservoirs must be of sufficient depth to contain the smoke layer and must not be less than 500 mm below an imperforate ceiling or roof.

(4) Within a multi-storey fire compartment—

a non-combustible bulkhead or smoke baffle/curtain must be provided around the underside of each opening into a building void to minimise the spread of smoke to other storeys; and

the depth of the bulkhead or smoke baffle must be not less than the depth of the smoke reservoir provided under (3) plus an additional 400 mm.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S21C4.