S21C7 Smoke exhaust system control
Specification 21 Smoke exhaust systems · NCC 2019: Spec E2.2b: 7
(1) Each smoke exhaust fan must be activated sequentially by smoke detectors complying with Specification 20 and arranged in zones to match the smoke reservoir served by the fan(s).
(2) Subject to (3) and (4), an air handling system (other than individual room units less than 1000 L/s and miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system must be automatically shut down on the activation of the smoke exhaust system.
(3) In a single storey fire compartment, air handling systems in all non fire-affected zones may operate on 100% outdoor air to provide make-up air to the fire-affected zone.
(4) Within a multi-storey fire compartment, air handling systems in all non fire-affected zones and storeys must operate at 100% outdoor air to provide make-up air to the fire-affected storey via building voids connecting storeys.
(5) Manual override control and indication together with operating instructions for use by emergency personnel must be provided adjacent to the fire indicator panel in accordance with the requirements of clauses 4.11 and 4.13 of AS 1668.1.
(6) Manual control for the smoke exhaust system must also be provided at a location normally used by the stage manager in a theatre.
(7) Power supply wiring to exhaust fans together with detection, control, and indication circuits (and where necessary to automatic make-up air supply arrangements) must comply with AS 1668.1.
Changed in NCC 2025. See NCC 2025 Volume One S21C7, or show what changed.
(1) Each smoke exhaust fan must be activated sequentially by … (other than individual room units less than 1000 L/s and miscellaneous exhaust air ventilation systems installed in accordance with Sections 5 and 6 of … adjacent to the fire indicator panel in accordance with the control and indication requirements of clauses 4.11 and 4.13 the smoke control operating instructions of AS 1668.1. (6) Manual control for the smoke exhaust … normally used by the stage manager in a theatre. (7) Power Electrical installations, including power supply wiring to exhaust fans together with detection, control, and control indication circuits (and where necessary to necessary, automatic make-up air supply arrangements) supply) must comply with the requirements of AS 1668.1.