Specification clause · NCC 2022 Volume One
S22C3 Controls
Specification 22 Smoke-and-heat vents · NCC 2019: Spec E2.2c: 2
Where a smoke-and-heat vent system is installed to comply with E2D14 to E2D20, then, in addition to thermally released link operation, smoke-and-heat vents must also be initiated by smoke detection complying with S20C6 and S20C8 and arranged in zones to match the smoke reservoirs.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S22C3.
Clauses referred to
- E2D14 Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)
- E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
- S20C6 Smoke detection for smoke control systems
- S20C8 System monitoring