Deemed-to-Satisfy Provision · NCC 2022 Volume One

E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)

Part E2 Smoke hazard management · NCC 2019: Table E2.2b

Open E2D20 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) The requirements of (2)—

apply to a Class 9b assembly building where the building or part of the building is used for a purpose other than—

as described in E2D16 to E2D19; or

a school; and

do not apply to—

sporting complexes (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than an indoor sports stadium with total spectator seating for more than 1000; or

churches and other places used solely for religious worship.

(2) Each fire compartment, other than one in a building referred to in (1)(b), having a floor area of more than 2000 m2 must be provided with—

an automatic smoke exhaust system complying with Specification 21; or

if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or

if the floor area of the fire compartment is not more than 5000 m2 and the building has a rise in storeys of not more than 2—

an automatic smoke detection and alarm system complying with Specification 20; or

a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another class.

Changed in NCC 2025. See NCC 2025 Volume One E2D20, or show what changed.

(1) The requirements of (2)— apply to a Class 9b … other than one in a building referred to in (1)(b), having a where the floor area of the Class 9b part is more than 2000 m2 must be provided with — an … throughout the whole building, including any part of another class.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet E2D20? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used