Specification clause · NCC 2022 Volume One
S23C2 Application
Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 1
apply to Class 3 residential care buildings; and
cover installation requirements for local fire indicator panels (or alarm panels) that provide information to staff when a fire alarm is activated.
(2) Clauses S23C8 and S23C9 describe requirements for connecting residential sprinkler systems in Class 2 and 3 buildings, or a residential care building, to a fire station or other approved monitoring service.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S23C2.
Clauses referred to
- S23C3 General requirements
- S23C7 Wiring
- S23C8 Connection to monitoring service
- S23C9 Indication at the fire indicator panel