Specification clause · NCC 2022 Volume One

S23C2 Application

Specification 23 Residential fire safety systems · NCC 2019: Spec E2.2d: 1

Open S23C2 on NCC Online ↗

(1) Clauses S23C3 to S23C7—

apply to Class 3 residential care buildings; and

cover installation requirements for local fire indicator panels (or alarm panels) that provide information to staff when a fire alarm is activated.

(2) Clauses S23C8 and S23C9 describe requirements for connecting residential sprinkler systems in Class 2 and 3 buildings, or a residential care building, to a fire station or other approved monitoring service.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S23C2.