Specification clause · NCC 2022 Volume One
S24C4 Cooling of lift shaft
Specification 24 Lift installations · NCC 2019: Spec E3.1: 4
While a lift in a lift shaft is in service, the cooling of the lift shaft must—
ensure that the dry bulb air temperature in the lift shaft does not exceed 40°C; and
if the cooling is by a ventilation system, be provided with an air change rate determined using a temperature rise of no more than 5 K.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S24C4.