Specification clause · NCC 2025 Volume One

S24C4 Cooling of lift shaft

Specification 24 Lift installations · NCC 2019: Spec E3.1: 4

Open S24C4 on NCC Online ↗

While a lift in a lift shaft is in service, the cooling of the lift shaft must—

ensure that the dry bulb air temperature in the lift shaft does not exceed 40°C; and

if the cooling is by a ventilation system, be provided with an air change rate determined using a temperature rise of no more than 5 K.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S24C4.

Defined terms used