S25C3 Illumination
Specification 25 Photoluminescent exit signs · NCC 2019: Spec E4.8: 3
A photoluminescent exit sign must—
be maintained in a continuously charged state by a minimum illumination of 100 lux at the face of the sign by a dedicated light source with a colour temperature not less than 4000 K; and
in the event of a power failure, continue to provide a minimum luminance of 30 mcd/m2 for not less than 90 minutes; and
have its performance verified by testing in accordance with ASTM E2073-10, except the activation illumination in clause 8.3 is replaced with 54 lux.