A photoluminescent exit sign must—

be maintained in a continuously charged state by a minimum illumination of 100 lux at the face of the sign by a dedicated light source with a colour temperature not less than 4000 K; and

in the event of a power failure, continue to provide a minimum luminance of 30 mcd/m2 for not less than 90 minutes; and

have its performance verified by testing in accordance with ASTM E2073-10, except the activation illumination in clause 8.3 is replaced with 54 lux.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One S25C3, or show what changed.