NCC 2022 Volume One
Specification 25 Photoluminescent exit signs
6 clauses · Open on NCC Online ↗
- S25C1 ScopeThis Specification contains requirements for photoluminescent exit signs.
- S25C2 ApplicationA photoluminescent exit sign must comply with Section 5 and Appendix D of AS/NZS 2293.1, except where varied by this Specification.
- S25C3 IlluminationA photoluminescent exit sign must— be maintained in a continuously charged state by a minimum illumination of 100 lux at the face of the sign by a…
- S25C4 Pictorial elementsPictorial elements on a photoluminescent exit sign must— where the colour white is used, be replaced with a photoluminescent material; and be not…
- S25C5 Viewing distanceThe maximum viewing distance in clause 5.6 of AS/NZS 2293.1 must not be more than 24 m.
- S25C6 Smoke control systemsSmoke control systems required by clause 5.3 of AS/NZS 2293.1 do not apply to a photoluminescent exit sign.