Specification 27 Accessible adult change facilities · NCC 2019: Spec F2.9: 3

Open S27C3 on NCC Online ↗

The hoist must—

provide a constant charge in-line room coverage hoist system (also known as an “XY” system or gantry) including 2 parallel fixed rails and a moving traverse rail; and

provide coverage over the entire room; and

have a maximum safe working load of not less than 180 kg; and

be capable of sustaining a static load of not less than 1.5 times the rated load; and

have a minimum lifting height of 2100 mm.