Specification clause · NCC 2025 Volume One
S27C3 Hoist
Specification 27 Accessible adult change facilities · NCC 2019: Spec F2.9: 3
The hoist must—
provide a constant charge in-line room coverage hoist system (also known as an “XY” system or gantry) including 2 parallel fixed rails and a moving traverse rail; and
provide coverage over the entire room; and
have a maximum safe working load of not less than 180 kg; and
be capable of sustaining a static load of not less than 1.5 times the rated load; and
have a minimum lifting height of 2100 mm.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S27C3.