S27C6 Fixtures and fittings
Specification 27 Accessible adult change facilities · NCC 2019: Spec F2.9: 6
(1) A vertical mirror must be provided at the washbasin, with a reflective surface that—
is not less than 600 mm wide; and
has its bottom edge not more than 900 mm above finished floor level; and
has its top edge not less than 1850 mm above finished floor level.
(2) If a second vertical mirror is provided in the facility, it must have a reflective surface that—
is not less than 600 mm wide; and
has its bottom edge not less than 600 mm above finished floor level; and
has its top edge not less than 1850 mm above finished floor level.
(3) Towel dispensers, hand dryers, soap dispensers and the like must be operable using one hand, and must be installed with their output or operative components—
between 900 mm and 1100 mm above finished floor level; and
not less than 500 mm from any internal corner.
(4) A soap dispenser must be installed above the integrated shelf required by S27C5(4).
(5) A clothing hook must be installed so that it is located—
at a height of between 1200 mm and 1350 mm above finished floor level; and
adjacent to the washbasin; and
not less than 500 mm from any internal corner.
(6) A sling hook with a minimum projection of 50 mm from the wall must be installed beside the change table at a height of 1500 mm above finished floor level.
(7) Disposal bins must be provided as follows:
A sanitary disposal bin in the corner adjacent to the toilet pan.
An incontinence pad disposal bin in the corner adjacent to the change table.