Specification clause · NCC 2022 Volume One

S32C2 Separation of stage areas, etc

Specification 32 Construction of proscenium walls · NCC 2019: Spec H1.3: 2

Open S32C2 on NCC Online ↗

(1) Dressing rooms, scene docks, property rooms, workshops, associated store rooms and other ancillary areas must be—

located on the stage side of the proscenium wall; and

separated from corridors and the like by construction having an FRL of not less than 60/60/60, and if of lightweight construction, complying with Specification 6.

(2) The stage and backstage must be separated from other parts of the building other than the audience seating area by construction having an FRL of not less than 60/60/60, and if of lightweight construction, complying with Specification 6.

(3) Any doorway in the construction referred to in (1) and (2) must be protected by a self-closing –/60/30 fire door.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S32C2.