Specification clause · NCC 2022 Volume One

S32C5 Protection of openings in proscenium wall

Specification 32 Construction of proscenium walls · NCC 2019: Spec H1.3: 5

Open S32C5 on NCC Online ↗

Every opening in a proscenium wall must be protected—

at the principal opening, by a curtain in accordance with S32C6 which is—

capable of closing the proscenium opening within 35 seconds either by gravity slide or motor assisted mechanisms; and

operated by a system of automatic heat activated devices, manually operated devices or push button emergency devices; and

able to be operated from either the stage side or the audience side of the curtain; and

at any doorway in the wall, by a self-closing –/60/30 fire door.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S32C5.