Specification 32 Construction of proscenium walls · NCC 2019: Spec H1.3: 5
Every opening in a proscenium wall must be protected—
at the principal opening, by a curtain in accordance with S32C6 which is—
capable of closing the proscenium opening within 35 seconds either by gravity slide or motor assisted mechanisms; and
operated by a system of automatic heat activated devices, manually operated devices or push button emergency devices; and
able to be operated from either the stage side or the audience side of the curtain; and
at any doorway in the wall, by a self-closing –/60/30 fire door.