Specification clause · NCC 2022 Volume One

S37C4 U-Value — Method 2 (Multiple Aspects)

Specification 37 Calculation of U-Value and solar admittance · NCC 2019: Spec J1.5a: 4

Open S37C4 on NCC Online ↗

(1) For the purposes of this method, a wall-glazing construction only includes the walls and glazing facing multiple aspects.

(2) The Total System U-Value of the wall component of a wall-glazing construction must be calculated as the inverse of the Total R-Value, including allowance for thermal bridging, in accordance with—

AS/NZS 4859.2; or

Specification 38 for spandrel panels.

(3) The Total System U-Value of a wall-glazing construction must be calculated as the area-weighted average of the Total System U-Value of each of the components of the wall-glazing construction.

(4) The Total System U-Value must not exceed the applicable value in J4D6(1).

Changed in NCC 2025. See NCC 2025 Volume One S37C4, or show what changed.