S39C2 Sub-floor space and soil thermal performance
Specification 39 Sub-floor and soil thermal performance · NCC 2019: Spec J1.6: 2
(1) Table S39C2a details the R-Values considered to be achieved by enclosed sub-floor spaces that are—
mechanically ventilated by not more than 1.5 air changes per hour; or
provided with not more than 150% of the aggregate sub-floor ventilation area required by Part F1 and are not mechanically ventilated.
(2) Table S39C2b details the R-Values considered to be achieved by the soil for floors that are in direct contact with the ground.
Table S39C2a R-Value of sub-floor spaces
Ratio of floor area (m2) to floor perimeter (m)
Sub-floor space R-Value
1.0
0.10
1.5
0.15
2.0
0.20
2.5
0.25
3.0
0.30
3.5
0.35
4.0
0.40
4.5
0.45
5.0
0.50
5.5
0.55
6.0
0.60
6.5
0.65
7.0
0.70
Table Notes
Where the ratio of floor area to floor perimeter is between the values stated, interpolation may be used to determine the sub-floor space R-Values.
Table S39C2b R-Value of soil in contact with a floor
Ratio of floor area (m2) to floor perimeter (m)
Wall thickness of 50 mm
Wall thickness of 100 mm
Wall thickness of 150 mm
Wall thickness of 200 mm
Wall thickness of 250 mm
Wall thickness of 300 mm
1.0
0.4
0.5
0.5
0.6
0.7
0.8
1.5
0.6
0.7
0.7
0.8
0.9
1.0
2.0
0.7
0.8
0.9
1.0
1.1
1.3
2.5
0.9
1.0
1.1
1.2
1.3
1.5
3.0
1.0
1.2
1.3
1.4
1.5
1.7
3.5
1.2
1.3
1.5
1.6
1.7
1.9
4.0
1.3
1.5
1.6
1.7
1.9
2.2
4.5
1.5
1.7
1.8
1.9
2.1
2.4
5.0
1.6
1.8
2.0
2.1
2.3
2.6
5.5
1.8
2.0
2.1
2.2
2.4
2.8
6.0
1.9
2.1
2.3
2.4
2.6
2.9
6.5
2.0
2.3
2.4
2.6
2.8
3.1
7.0
2.2
2.4
2.6
2.7
3.0
3.3
Table Notes
Where a wall thickness or ratio of floor area to floor perimeter is between the values stated, interpolation may be used to determine the soil R-Value.
Wall thickness means the thickness of the envelope wall that sits on or around the slab.