S4C2 Roof cladding
Specification 4 Design of buildings in cyclonic areas · NCC 2019: Spec B1.2: 2
Test for strength: Metal roof cladding, its connections and immediate supporting members must be capable of remaining in position notwithstanding any permanent distortion, fracture or damage that might occur in the sheet or fastenings under the pressure sequences A to G defined in Table S4C2.
Table S4C2 Low-high-low pressure sequence
Sequence
Number of cycles
Load
A
4500
0 to 0.45 Pt
B
600
0 to 0.6 Pt
C
80
0 to 0.8 Pt
D
1
0 to 1.0 Pt
E
80
0 to 0.8 Pt
F
600
0 to 0.6 Pt
G
4500
0 to 0.45 Pt
Table Notes
Pt is the ultimate limit state wind pressure on internal and external surfaces as determined in accordance with AS/NZS 1170.2, modified by an appropriate factor for variability, as determined in accordance with Table B1 of AS/NZS 1170.0.
The rate of load cycling must be less than 3 Hz.
The single load cycle (sequence D) must be held for a minimum of 10 seconds.