Table · NCC 2022 Volume One
Table S4C2 Low-high-low pressure sequence
Specification 4 Design of buildings in cyclonic areas
| Sequence | Number of cycles | Load |
|---|---|---|
| A | 4500 | 0 to 0.45 Pt |
| B | 600 | 0 to 0.6 Pt |
| C | 80 | 0 to 0.8 Pt |
| D | 1 | 0 to 1.0 Pt |
| E | 80 | 0 to 0.8 Pt |
| F | 600 | 0 to 0.6 Pt |
| G | 4500 | 0 to 0.45 Pt |
Table Notes
Pt is the ultimate limit state wind pressure on internal and external surfaces as determined in accordance with AS/NZS 1170.2, modified by an appropriate factor for variability, as determined in accordance with Table B1 of AS/NZS 1170.0.
The rate of load cycling must be less than 3 Hz.
The single load cycle (sequence D) must be held for a minimum of 10 seconds.
Table for S4C2 Roof cladding