Specification clause · NCC 2022 Volume One
S5C13 Type A fire-resisting construction — floor loading of Class 5 and 9b buildings: Concession
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.3
If a floor in a Class 5 or 9b building is designed for a live load not exceeding 3 kPa—
the floor next above (including floor beams) may have an FRL of 90/90/90; or
the roof, if that is next above (including roof beams), may have an FRL of 90/60/30.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S5C13.