Specification clause · NCC 2025 Volume One

S5C13 Type A fire-resisting construction — floor loading of Class 5 and 9b buildings: Concession

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.3

Open S5C13 on NCC Online ↗

If a floor in a Class 5 or 9b building is designed for a live load not exceeding 3 kPa—

the floor next above (including floor beams) may have an FRL of 90/90/90; or

the roof, if that is next above (including roof beams), may have an FRL of 90/60/30.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S5C13.