Specification clause · NCC 2022 Volume One
S5C15 Type A fire-resisting construction — roof: Concession
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.5
A roof need not comply with Table S5C11g if its covering is non-combustible and the building—
has a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 installed throughout; or
has a rise in storeys of 3 or less; or
is of Class 2 or 3; or
has an effective height of not more than 25 m and the ceiling immediately below the roof has a resistance to the incipient spread of fire to the roof space of not less than 60 minutes.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S5C15.