Specification clause · NCC 2025 Volume One

S5C15 Type A fire-resisting construction — roof: Concession

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.5

Open S5C15 on NCC Online ↗

A roof need not comply with Table S5C11g if its covering is non-combustible and the building—

has a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 installed throughout; or

has a rise in storeys of 3 or less; or

is of Class 2 or 3; or

has an effective height of not more than 25 m and the ceiling immediately below the roof has a resistance to the incipient spread of fire to the roof space of not less than 60 minutes.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S5C15.

Defined terms used