Specification clause · NCC 2022 Volume One

S5C18 Type A fire-resisting construction — open spectator stands and indoor sports stadiums: Concession

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.8

Open S5C18 on NCC Online ↗

In an open spectator stand or indoor sports stadium, the following building elements need not have the FRL specified in Tables S5C11a, S5C11b, S5C11c, S5C11e and S5C11g:

The roof if it is non-combustible.

Columns and loadbearing walls supporting only the roof if they are non-combustible.

Any non-loadbearing part of an external wall less than 3 m—

from any fire-source feature to which it is exposed if it has an FRL of not less than –/60/60 and is non-combustible; or

from an external wall of another open spectator stand if it is non-combustible.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One S5C18.