S5C19 Type A fire-resisting construction — carparks
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.9 and Table 3.9
(1) Notwithstanding S5C11, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below another classification, and the floor separating the classifications complies with C3D10; or
which is located above another Class 7 part of the building not used for carparking, and the floor separating the parts complies with Table S5C11g for a Class 7 part other than a carpark; or
which is located below another Class 7 part of the building not used for carparking, and the floor separating the parts complies with this clause.
(2) For the purposes of this clause, a carpark—
includes—
an administration area associated with the functioning of the carpark; and
where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units, each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
excludes—
except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.
(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:
External wall:
Less than 3 m from a fire-source feature to which it is exposed:
Loadbearing: 60/60/60.
Non-loadbearing: –/60/60.
3 m or more from a fire-source feature to which it is exposed: –/–/–.
Internal wall:
Loadbearing, other than one supporting only the roof (not used for carparking): 60/–/–.
Supporting only the roof (not used for carparking): –/–/–.
Non-loadbearing: –/–/–.
Fire wall:
From the direction used as a carpark: 60/60/60.
From the direction not used as a carpark: as required by Table S5C11d.
Columns:
Supporting only the roof (not used for carparking) and 3 m or more from a fire-source feature to which it is exposed: –/–/–.
Steel column, other than one covered by (i) and one that does not support a part of a building that is not used as a carpark—
60/–/–; or
an ESA/M of not greater than 26m2/tonne.
Any other column not covered by (i) or (ii): 60/–/–.
Beams:
Steel floor beam in continuous contact with a concrete floor slab—
60/–/–; or
an ESA/M of not greater than 30m2/tonne.
Any other beam: 60/–/–.
Fire-resisting lift and stair shaft (within the carpark only): 60/60/60.
Floor slab and vehicle ramp: 60/60/60.
Roof (not used for carparking): –/–/–.
(4) For the purposes of sub-clause (3):
ESA/M means the ratio of exposed surface area to mass per unit length.
Refer to Specification 17 for special requirements for a sprinkler system in a carpark complying with (3) and located within a multi-classified building.
Changed in NCC 2025. See NCC 2025 Volume One S5C19, or show what changed.
(1) Notwithstanding S5C11, a carpark may comply with this clause if it is — an open-deck carpark which is a separate building; or is protected with a sprinkler system (other than a FPAA101D or … remaining part by a fire wall; or which is located above or below above, but not below, another classification, and the floor separating the classifications complies with … m from a fire-source feature to which it is exposed: Loadbearing: Load bearing: 60/60/60. Non-loadbearing: Non-load bearing: –/60/60. 3 m or more from a fire-source feature to which it is exposed: –/–/–. Internal wall: Loadbearing, Load bearing, other than one supporting only the roof (not used for carparking): 60/–/–. Supporting only the roof (not used for carparking): –/–/–. Non-loadbearing: Non-load bearing: –/–/–. Fire wall: From the direction used as a carpark: … carpark complying with (3) and located within a multi-classified building.