S5C22 Type B fire-resisting construction — carparks
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 4.2 and Table 4.2
(1) Notwithstanding S5C21, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—
a separate building; or
a part of a building, and if occupying only part of a storey, is separated from the remaining part by a fire wall.
(2) For the purposes of this clause, a carpark—
includes—
an administration area associated with the functioning of the carpark; and
where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
excludes—
except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.
(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:
External walls:
Less than 3 m from a fire-source feature to which it is exposed:
Loadbearing: 60/60/60.
Non-loadbearing:–/60/60.
3 m or more from a fire-source feature to which it is exposed: –/–/–.
Internal walls:
Loadbearing, other than one supporting only the roof (not used for carparking): 60/–/–.
Supporting only the roof (not used for carparking): –/–/–.
Non-loadbearing: –/–/–.
Fire walls:
From the direction used as a carpark: 60/60/60.
From the direction not used as a carpark: as required by Table S5C21d.
Columns:
Supporting only the roof (not used for carparking) and 3 m or more from a fire-source feature to which it is exposed: –/–/–.
Steel column, other than one covered by (i) and one that does not support a part of a building that is not used as a carpark—
60/–/–; or
an ESA/M of not greater than 26 m2/tonne.
Any other column not covered by (i) or (ii): 60/–/–.
Beams:
Steel floor beam less than 3 m from a fire-source feature in continuous contact with a concrete floor slab—
60/–/–; or
an ESA/M of not greater than 30 m2/tonne.
Any other beam less than 3 m from a fire-source feature: 60/–/–.
Any beam 3 m or more from a fire-source feature: –/–/–.
Lift shaft: –/–/–.
Fire-resisting stair shaft (within the carpark only): 60/60/60.
Roof, floor slab and vehicle ramp: –/–/–.
(4) For the purposes of (3), ESA/M means the ratio of exposed surface area to mass per unit length.
Changed in NCC 2025. See NCC 2025 Volume One S5C22, or show what changed.
(1) Notwithstanding S5C21, a carpark may comply with this clause if it is — an open-deck carpark which is a separate building; or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is … m from a fire-source feature to which it is exposed: Loadbearing: Load bearing: 60/60/60. Non-loadbearing:–/60/60. Non-load bearing: –/60/60. 3 m or more from a fire-source feature to which it is exposed: –/–/–. Internal walls: Loadbearing, Load bearing, other than one supporting only the roof (not used for carparking): 60/–/–. Supporting only the roof (not used for carparking): –/–/–. Non-loadbearing: Non-load bearing: –/–/–. Fire walls: From the direction used as a carpark: … ratio of exposed surface area to mass per unit length.
Removed words are struck through; added words are highlighted. Comparison of the text only.