S5C23 Type B fire-resisting construction — Class 2 and 3 buildings: Concession
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 4.3
(1) In a Class 2 or 3 building with a rise in storeys of not more than 2—
notwithstanding C2D10(1) and (2), timber framing may be used for—
external walls; and
common walls; and
the floor framing of lifts pits; and
non-loadbearing internal walls which are required to be fire-resisting; and
non-loadbearing shafts, except shafts used for the discharge of hot products of combustion; and
notwithstanding S5C21(1)(d), for loadbearing internal walls and loadbearing fire walls—
timber framing may be used; and
non-combustible materials may be used; and
notwithstanding S5C3(1)(c), timber framing may be used for a part of a building that provides support to a part of a building constructed of timber framing or non-combustible material in accordance with (a) and (b).
(2) A Class 2 or 3 building having a rise in storeys of not more than 2 may have the top storey constructed in accordance with (1) provided—
the lowest storey is used solely for the purpose of parking motor vehicles or for some other ancillary purpose; and
the lowest storey is constructed of concrete or masonry including the floor between it and the Class 2 or 3 part of the building above; and
the lowest storey and the storey above are separated by construction having an FRL of not less than 90/90/90 with no openings or penetrations that would reduce the fire-resisting performance of that construction except that a doorway in that construction may be protected by a –/60/30 self-closing fire door.
(3) In a Class 2 or 3 building complying with (1) or (2) and fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, any FRL criterion prescribed in Tables S5C21a, S5C21d, S5C21e, S5C21f and S5C21g; and —
for any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
for any non-loadbearing internal wall, need not apply, if—
it is lined on both sides with 13 mm standard grade plasterboard or similar non-combustible material; and
it extends—
to the underside of the floor next above if that floor has an FRL of at least 30/30/30 or is lined on the underside with a fire-protective covering; or
to the underside of a ceiling with a resistance to the incipient spread of fire of 60 minutes; or
to the underside of a non-combustible roof covering; and
any insulation installed in the cavity of the wall is non-combustible; and
any construction joints, spaces and the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material.
Changed in NCC 2025. See NCC 2025 Volume One S5C23, or show what changed.
(1) In a Class 2 or 3 building with a … common walls; and the floor framing of lifts pits; and non-loadbearing non-load bearing internal walls which are required to be fire-resisting; and non-loadbearing non-load bearing shafts, except shafts used for the discharge of hot products of combustion; and notwithstanding S5C21(1)(d), for loadbearing load bearing internal walls and loadbearing load bearing fire walls — timber framing may be used; and non-combustible … non-combustible material in accordance with (a) and (b). (2) A Class 2 or 3 building having a rise in storeys of not more than … motor vehicles or for some other ancillary purpose; and the remaining storeys are Class 2 or 3; and the lowest storey is storey’s load bearing elements are constructed of concrete or masonry masonry, including the floor between it and the Class 2 or … S5C21a, S5C21d, S5C21e, S5C21f and S5C21g; and — for any loadbearing load bearing wall, may be reduced to 60, except any FRL criterion … be maintained when tested from the outside; and for any non-loadbearing non-load bearing internal wall, need not apply, if — it is lined … is smoke sealed with intumescent putty or other suitable material.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Clauses referred to
- C2D10 Non-combustible building elements
- S5C21 Type B fire-resisting construction — fire-resistance of building elements