S6C10 Test methods
Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 5
Tests must be carried out in accordance with the following:
Material tests — The methods specified for the constituent materials of the construction of the standards adopted by reference in the NCC.
For resistance to static pressure — The provisions for testing walls under transverse load in ASTM E72-15, except that—
support conditions must be as specified in S6C9; and
equivalent load shall mean the quarter-point load that produces the same deflection or central moment as appropriate; and
the timber species nominated in that standard may be substituted with a different species.
For resistance to impact — The provisions for testing wall systems in ASTM E695-03, except that—
the point of impact must be set 1.5 m above finished floor level or 1.5 m above the part of the specimen that corresponds to finished floor level; and
the impact bag must be not less than 225 mm in diameter and not more than 260 mm in diameter and have a mass of not less than 27.2 kg or more than 27.3 kg; and
the mass must be achieved by putting loose, dry sand into the bag and must be adjusted before each series of impact tests; and
where the impact bag and suspension cannot be vertical at the instant of impact on a curved surface or an inclined surface, the height of drop is the net height at the point of impact.
For resistance to surface indentation — The test for resistance to surface indentation must be carried out at three points on the surface of an undamaged sample sheet as follows:
A steel ball of 10 mm diameter with a load of 150 N must be placed gently on the surface of the sheet and allowed to remain in position for 5 minutes.
The ball and load must then be removed and the diameter of each impression of the ball on the surface measured.
For resistance of lift shaft construction to repetitive load — As for (b) except that—
it is sufficient to test one specimen with the pressure applied from the side of the construction on which the lift will operate; and
the load must be applied dynamically at a frequency not less than 1 Hz and not more than 3 Hz; and
equivalent load shall mean the quarter-point load that produces the same central moment as the distributed load.