S6C10 Test methods

Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 5

Open S6C10 on NCC Online ↗

Tests must be carried out in accordance with the following:

Material tests — The methods specified for the constituent materials of the construction of the standards adopted by reference in the NCC.

For resistance to static pressure — The provisions for testing walls under transverse load in ASTM E72-15, except that—

support conditions must be as specified in S6C9; and

equivalent load shall mean the quarter-point load that produces the same deflection or central moment as appropriate; and

the timber species nominated in that standard may be substituted with a different species.

For resistance to impact — The provisions for testing wall systems in ASTM E695-03, except that—

the point of impact must be set 1.5 m above finished floor level or 1.5 m above the part of the specimen that corresponds to finished floor level; and

the impact bag must be not less than 225 mm in diameter and not more than 260 mm in diameter and have a mass of not less than 27.2 kg or more than 27.3 kg; and

the mass must be achieved by putting loose, dry sand into the bag and must be adjusted before each series of impact tests; and

where the impact bag and suspension cannot be vertical at the instant of impact on a curved surface or an inclined surface, the height of drop is the net height at the point of impact.

For resistance to surface indentation — The test for resistance to surface indentation must be carried out at three points on the surface of an undamaged sample sheet as follows:

A steel ball of 10 mm diameter with a load of 150 N must be placed gently on the surface of the sheet and allowed to remain in position for 5 minutes.

The ball and load must then be removed and the diameter of each impression of the ball on the surface measured.

For resistance of lift shaft construction to repetitive load — As for (b) except that—

it is sufficient to test one specimen with the pressure applied from the side of the construction on which the lift will operate; and

the load must be applied dynamically at a frequency not less than 1 Hz and not more than 3 Hz; and

equivalent load shall mean the quarter-point load that produces the same central moment as the distributed load.