S6C11 Criteria for compliance
Specification 6 Structural tests for lightweight construction · NCC 2019: Spec C1.8: 6
The wall system or the specimen of it must fulfil the following criteria:
Materials — Materials must comply with the applicable standard adopted by reference in the NCC.
Damage — There must be no crack, penetration or permanent surface-deformation to a depth of more than 0.5 mm or any other non-elastic deformation or fastener failure.
Deflection — Static pressure — Under static pressure the deflection must not be more than—
1/240th of the height between supports; or
for construction other than a lift shaft — 30 mm; or
for a lift shaft — 20 mm.
Deflection — Impact — Under impact the instantaneous deflection must not be more than—
1/120th of the height of the wall between supports; or
for construction other than a lift shaft — 30 mm; or
for a lift shaft— 20 mm.
Surface indentation — No impression must be more than 5 mm in diameter.