South Australia variation · NCC 2022 Volume One

SA C2D16 Class 7b bulk grain storage facilities

Part C2 Fire resistance and stability

Open on NCC Online ↗

Insert SA clause C2D16 in clause C2D16 as follows:

The external walls of a bulk grain storage facility need not be of fire-resisting construction if—

The external walls are 3 m or more from an allotment boundary and more than 6 m from any other building on the same allotment, other than a Class 10 building; and

a fire separation space of not less than 2 m is provided between cell type silos; and

the external walls are—

of non-combustible construction; or

of Type C construction.

Not in NCC 2025. No SA C2D16 in NCC 2025 Volume One.