South Australia variation · NCC 2022 Volume One
SA C2D16 Class 7b bulk grain storage facilities
Part C2 Fire resistance and stability
Insert SA clause C2D16 in clause C2D16 as follows:
The external walls of a bulk grain storage facility need not be of fire-resisting construction if—
The external walls are 3 m or more from an allotment boundary and more than 6 m from any other building on the same allotment, other than a Class 10 building; and
a fire separation space of not less than 2 m is provided between cell type silos; and
the external walls are—
of non-combustible construction; or
of Type C construction.
Not in NCC 2025. No SA C2D16 in NCC 2025 Volume One.