NCC 2022 Volume One
South Australia variations
56 SA variations to NCC 2022 Volume One: clauses replaced, added or deleted in South Australia. Search with SA variations.
- SA A6G7 Class 6 buildingsDelete clause A6G7 and insert SA A6G7 as follows: A Class 6 building is a shop or other building for the sale of goods by retail or the supply of…
- SA B1D6 Construction of buildings in flood hazard areasThis clause been deliberately left blank
- SA B1P4 Buildings in flood areasThis clause been deliberately left blank
- SA C2D2 Type of construction requiredDelete subclause C2D2(1) and insert SA C2D2(1) as follows: (1) The minimum Type of fire-resisting construction of a building must be determined in…
- SA C2D16 Class 7b bulk grain storage facilitiesInsert SA clause C2D16 in clause C2D16 as follows: The external walls of a bulk grain storage facility need not be of fire-resisting construction…
- SA C3D16 Class 2 external walls exposed to brush fencesInsert SA clause C3D16 in clause C3D16 as follows: Where the distance between the external wall of a Class 2 building and a brush fence is less than…
- SA C3D17 Bulk grain storage facilitiesInsert SA clause C3D17 in clause C3D17 as follows: Underground passageways in a bulk grain storage facility must be separated from other parts of…
- SA C4D18 Protection of openings – bulk grain storage facilitiesInsert SA clause C4D18 in clause C4D18 as follows: Where external stairs, ramps or ladders are used as an exit in a bulk grain storage facility, any…
- SA D2D3 Number of exits requiredDelete subclause D2D3(2) and insert SA D2D3(2) as follows: (2) Class 2 to 8 buildings — In addition to any horizontal exit, not less than 2 exits…
- SA D2D4 When fire-isolated stairways and ramps are requiredDelete subclause D2D4(2) and insert SA D2D4(2) as follows: (2) Class 5, 6, 7, 8 or 9 buildings — Every stairway or ramp serving as a required exit…
- SA D2D5 Exit travel distancesInsert SA subclause D2D5(7) in clause D2D5 as follows: (7) Farm buildings — Notwithstanding (3), in a farm building— no point on the floor must be…
- SA D2D6 Distance between alternative exitsDelete clause D2D6 and insert SA D2D6 as follows: Exits that are required as alternative means of egress must be— distributed as uniformly as…
- SA D2D14 Travel by non-fire-isolated stairways or rampsInsert SA subclause D2D14(7) in clause D2D14 as follows: (7) In a bulk grain storage facility, the distance from any point on the floor to a point…
- SA D2D21 Plant rooms, lift machine rooms and electricity network substations: ConcessionInsert SA subclause D2D21(3) in clause D2D21 as follows: (3) In a bulk grain storage facility, a stair or ladder complying with AS 1657 may be used…
- SA D3D16 ThresholdsDelete clause D3D16 and insert SA D3D16 as follows: (1) The threshold of a doorway must not incorporate a step or ramp at any point closer to the…
- SA D3D23 Fixed platforms, walkways, stairways and laddersDelete clause D3D23 and insert SA D3D23 as follows: A fixed platform, walkway, stairway, ladder and any going and riser, landing, handrail or…
- SA D3D25 Swinging doorsDelete subclause D3D25(1) and insert SA D3D25(1) as follows: (1) A swinging door in a required exit or forming part of a required exit— must not…
- SA D4D2 General building access requirementsDelete subclause D4D2(4) and insert SA D4D2(4) as follows: (4) For a Class 2 building, access requirements are as follows: Common areas: From a…
- SA D4D5 ExemptionsDelete clause D4D5 and insert SA D4D5 as follows: The following areas are not required to be accessible: An area where access would be inappropriate…
- SA E1D2 Fire hydrantsInsert SA subclause E1D2(5) in clause E1D2 as follows: (5) In a farm building, in lieu of providing a fire hydrant system in accordance with (2),…
- SA E1D3 Fire hose reelsDelete subclause E1D3(1) and insert SA E1D3(1) as follows: (1) E1D3 does not apply to— a Class 2, 3 or 5 building or Class 4 part of a building; or…
- SA E1D14 Portable fire extinguishersInsert SA subclause E1D14(7) in clause E1D14 as follows: (7) For Class A fire risks in a farm building the requirements of (1) need not be provided…
- SA E2D1 Deemed-to-Satisfy ProvisionsDelete subclause E2D1(1) and insert SA E2D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements E2P1 and…
- SA E2D22 Smoke venting in bulk grain storage facilitiesInsert SA clause E2D22 in clause E2D22 as follows: In bulk grain storage facility— suitable natural smoke venting by fixed vents must be provided at…
- SA E4D2 Emergency lighting requirementsDelete clause E4D2 and insert SA E4D2 as follows: An emergency lighting system must be installed— in every fire-isolated stairway, fire-isolated…
- SA E4D5 Exit signsDelete clause E4D5 and insert SA E4D5 as follows: An exit sign must be clearly visible to persons approaching the exit, and must be installed on,…
- SA E4D8 Design and operation of exit signsDelete clause E4D8 and insert SA E4D8 as follows: (1) Every required exit sign must— comply with— AS/NZS 2293.1; or for a photoluminescent exit…
- SA F1D1 Deemed-to-Satisfy ProvisionsDelete subclause F1D1(1) and insert SA F1D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements F1P1 to F1P3…
- SA F1D6 Damp-proofingDelete subclause F1D6(2) and insert SA F1D6(2) as follows: (2) Damp-proof courses must exhibit long term resistance to degradation by dissolved…
- SA F1D7 Damp-proofing of floors on the groundDelete clause F1D7 and insert SA F1D7 as follows: (1) If a floor of a room is laid on the ground or on fill, a damp-proofing membrane complying with…
- SA F1P4 Rising dampDelete clause F1P4 and insert SA F1P4 as follows: (1) Moisture from the ground must be prevented from causing— undue dampness or deterioration of…
- SA F2D2 Wet area constructionDelete subclause F2D2(1) and insert SA F2D2(1) as follows: (1) In a Class 2 and 3 building and a Class 4 part of a building, building elements in…
- SA F2D4 Provision of floor wastesDelete clause F2D4 and insert SA F2D4 as follows: (1) A wet area provided with a vessel in accordance with F4D2, F4D4 and F4D5 must have the floor…
- SA F2P1 Wet area overflowsDelete clause F2P1 and insert SA F2P1 as follows: Overflow from a bathroom, laundry facility or the like must be prevented from penetrating to…
- SA F2P3 Prevention of surface water accumulationInsert SA clause F2P3 in clause F2P3 as follows: In laundries, bathrooms or rooms containing shower facilities the floors must be installed in a…
- SA F4D6 Accessible unisex sanitary compartmentsDelete subclause F4D6(1) and insert SA F4D6(1) as follows: (1) Where required by F4D5(a), the minimum number of accessible unisex sanitary…
- SA F4D7 Accessible unisex showersDelete subclause F4D7(1) and insert SA F4D7(1) as follows: (1) Where required by F4D5(b), the minimum number of accessible unisex showers for each…
- SA F6D6 Ventilation of roomsDelete clause F6D6 and insert SA F6D6 as follows: A habitable room, office, shop, factory, workroom, sanitary compartment, bathroom, shower room,…
- SA G1D2 Swimming poolsDelete clause G1D2 and insert SA G1D2 as follows: (1) A swimming pool with a depth of water more than 300 mm and which is associated with a Class 2…
- SA G1P2 Swimming pool access and water recirculation systemsDelete clause G1P2 and insert SA G1P2 as follows: (1) A barrier must be provided to a swimming pool and must— be continuous for the full extent of…
- SA G5D1 Deemed-to-Satisfy ProvisionsDelete subclause G5D1(1) and insert SA G5D1(1) as follows: (1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements G5P1 and…
- SA G5D5 Bushfire attack levelsInsert SA clause G5D5 in clause G5D5 as follows: Where a site is located in a designated bushfire prone area, the bushfire attack level that applies…
- SA G8D1 Deemed-to-Satisfy ProvisionsPerformance RequirementsSA G8P1 and SA G8P2 are satisfied by complying with SA G8D2 to SA G8D4.
- SA G8D2 Application of PartSA G8D3 and SA G8D4 apply to Class 2 to 9 buildings.
- SA G8D3 Access for window cleaningWhere any part of a window in a building is more than 5.5 m above ground level, access to the external surface of the window for minor maintenance…
- SA G8D4 Access for inspection and maintenance between buildingsEvery part of an external wall of a building must be not less than 600 mm from— the external wall of any other building on the same allotment,…
- SA G8F1 Window cleaningA building is to provide people with safe conditions for carrying out window cleaning operations.
- SA G8F2 Hazardous conditionsThe space between buildings must not allow hazardous conditions to arise due to accumulation of rubbish that cannot readily be removed.
- SA G8O1 ObjectiveThe Objectives of this Part are— to safeguard people from injury while cleaning windows; and to safeguard people from injury or illness resulting…
- SA G8P1 Window cleaningWhere any part of a window in a building is more than 5.5 m above ground level, provision must be made for safe access to the external surface of…
- SA G8P2 Hazardous conditionsThe space between buildings must be sufficient to allow access for inspection and maintenance, to avoid hazardous conditions arising due to…
- SA G9D1 Deemed-to-Satisfy ProvisionsPerformance RequirementSA G9P1 is satisfied by complying with SA G9D2 and SA G9D3.
- SA G9D2 Application of PartSA G9D3 applies to Class 2 to 9 buildings.
- SA G9D3 Attachments to buildingsAn attachment to a building that is in the nature of a balcony or awning, bridge, gangway, hoarding or trade sign, sky sign, mast, flagpole, tower,…
- SA G9P1 Attachments to buildingsAn attachment to a building must incorporate features that will— protect it against corrosion; and collect and discharge water run-off safely; and…
- SA I3D1 Application of PartThe provisions of Part I3 do not apply in South Australia. Notes Additional requirements for farm buildings are contained in individual SA variation…