South Australia variation · NCC 2022 Volume One

SA C3D17 Bulk grain storage facilities

Part C3 Compartmentation and separation

Open on NCC Online ↗

Insert SA clause C3D17 in clause C3D17 as follows:

Underground passageways in a bulk grain storage facility must be separated from other parts of the building by smoke-proof walls and smoke-proof doors complying with Specification 11.

Not in NCC 2025. No SA C3D17 in NCC 2025 Volume One.